The colors that tell you what a fiber cable is: jacket colors by fiber type, connector colors, and the standard 12-fiber color order. Based on TIA-598 and common industry practice. Look up any fiber by number below, or print the chart for the wall.
Enter a fiber number to see its buffer tube and its color in that tube. Most loose-tube cables have 12 fibers per tube; check the cable's legend if yours differs.
Fiber 30 is in tube 3 (green): the 6th fiber in that tube, white.
Fiber optic color code (TIA-598, TIA-568.3-D) · networksketch.com/fiber-color-code
The outer jacket of a patch cord or cable usually tells you the fiber type at a glance.
| Fiber type | Core / cladding | Jacket color | Typical use |
|---|---|---|---|
| OS1 / OS2 single-mode | 9/125 µm | Yellow | Long runs, between buildings, carrier hand-offs |
| OM1 multimode | 62.5/125 µm | Orange | Older installs, 1 Gbps |
| OM2 multimode | 50/125 µm | Orange | Older installs, 1 Gbps over longer runs |
| OM3 multimode | 50/125 µm, laser-optimized | Aqua | 10 Gbps in the building |
| OM4 multimode | 50/125 µm, laser-optimized | Aqua, or Erika violet (common in Europe) | 10 to 100 Gbps in the data center |
| OM5 wideband multimode | 50/125 µm | Lime green | Short-wave WDM, 40/100 Gbps |
| Outside plant (any type) | Single-mode or multimode | Black | Underground, aerial and between buildings: black resists UV. Read the print for the fiber type. |
TIA-598 sets these colors for premises cable and allows other colors when the fiber type is printed on the jacket, so the printed legend has the final word. Erika violet for OM4 is a regional and vendor convention, not part of TIA-598.
The connector body (and the adapter it plugs into) shows the fiber mode and, for single-mode, the polish. TIA-568.3-D identifies fiber type by connector and adapter color this way; it's a convention, so check the cable too.
| Connector | Color | Notes |
|---|---|---|
| Single-mode UPC | Blue | Flat polish. The most common single-mode connector. |
| Single-mode APC | Green | 8° angled polish, lower back-reflection (PON, video). Never mate APC with UPC. |
| Multimode OM1 / OM2 | Beige (sometimes black for OM2) | TIA-568.3-D: beige for 62.5 µm, black for 50 µm. Beige is common on both. |
| Multimode OM3 / OM4 | Aqua (OM4 sometimes heather violet) | |
| Multimode OM5 | Lime green |
Fibers in a tube, and tubes in a cable, follow the same order. Fibers 13 to 24 repeat the same twelve colors with a black stripe or dash, except fiber 20 (black), which gets a yellow one.
Colors are conventions, not guarantees: some vendors and older installs differ, and patch cords get swapped. Check the cable's printed legend and test before you trust a color.
Fibers 13 to 24 repeat the twelve colors with a black stripe or dash (a "tracer"), except fiber 20: black with a yellow stripe, so it still stands out. Ribbon fibers and buffer tubes 13 to 24 follow the same rule.
In a loose-tube cable the buffer tubes use the same color order as the fibers: tube 1 is blue, tube 2 orange, and so on. With twelve fibers per tube, a fiber's tube is its number divided by 12, rounded up, and its color is its position inside that tube.
| Cable | Tubes (12 fibers each) | Tube colors, in order |
|---|---|---|
| 24-fiber | 2 tubes of 12 | Blue, Orange |
| 48-fiber | 4 tubes of 12 | Blue, Orange, Green, Brown |
| 72-fiber | 6 tubes of 12 | Blue, Orange, Green, Brown, Slate, White |
| 96-fiber | 8 tubes of 12 | Blue, Orange, Green, Brown, Slate, White, Red, Black |
| 144-fiber | 12 tubes of 12 | Blue, Orange, Green, Brown, Slate, White, Red, Black, Yellow, Violet, Rose, Aqua |
Example: fiber 30 in a 144-fiber cable is in tube 3 (green), position 6 (white): the white fiber in the green tube. Fiber 145 and up start again with striped tubes. Some cables put 6 or 24 fibers in a tube, so check the cable's legend before you count.
For transmit and receive pairs, fibers are usually paired in order: 1 with 2, 3 with 4, and so on.
| Pair | Fibers | Colors |
|---|---|---|
| Pair 1 | Fibers 1 and 2 | Blue + Orange |
| Pair 2 | Fibers 3 and 4 | Green + Brown |
| Pair 3 | Fibers 5 and 6 | Slate + White |
| Pair 4 | Fibers 7 and 8 | Red + Black |
| Pair 5 | Fibers 9 and 10 | Yellow + Violet |
| Pair 6 | Fibers 11 and 12 | Rose + Aqua |
Duplex patch cords have their own convention: on LC duplex cords the two legs are often A and B, or marked with colored boots. Polarity (A-to-B) matters more than the colors there.
Fibers 1 to 12 are blue, orange, green, brown, slate, white, red, black, yellow, violet, rose and aqua. Fibers 13 to 24 repeat those colors with a black stripe, except fiber 20, which is black with a yellow stripe. In a loose-tube 24-fiber cable that's usually two tubes: blue (fibers 1 to 12) and orange (fibers 13 to 24), each with fibers colored 1 to 12.
Blue with a black stripe in a single 24-fiber group or ribbon. In a cable with 12 fibers per tube, fiber 13 is the blue fiber in the second (orange) tube.
Divide the fiber number by 12 and round up to get the tube, then count its position in that tube. Fiber 30 is in tube 3 (green), position 6 (white). Fiber 144 is the aqua fiber in the aqua tube.
The jacket of single-mode (OS1/OS2) fiber is yellow. Single-mode connectors are blue for UPC (flat polish) and green for APC (angled polish).
Usually black, whatever the fiber inside, because black jackets resist sunlight. The fiber type is printed on the jacket; indoor-outdoor cables often keep the indoor color (yellow, aqua, orange).
Yes: TIA-598 in North America. Vendors and older installs sometimes differ, so check the cable's printed legend and test before relying on a color.
In NetworkSketch, every link has a media type, and the line takes its color: yellow for single-mode, orange for OM1/OM2, aqua for OM3/OM4, lime for OM5. The media type key builds itself from the cables you used. For copper runs, see the Ethernet cable color code (T568A and T568B). Planning the link? The fiber distance chart shows how far each optic reaches on each fiber, and the fiber loss calculator checks the loss budget.