Free tool

Rack elevation diagram planner

Updated

Lay out a server or network rack unit by unit. Add gear, drag it into place, and see how much space and power is left. Export the rack diagram as SVG, PNG or CSV, or print it. It runs in your browser.

What a rack elevation diagram is

A rack elevation is a to-scale drawing of the front (or rear) of an equipment rack, showing which device sits in which rack units. It answers the questions that come up during an install or an outage: where the firewall is, which switch a patch panel feeds, and whether a new 2U server will fit.

Racks for network and server gear are 19 inches wide between the mounting ears (EIA-310). Height is counted in rack units: 1U is 1.75 in (44.45 mm). Devices are sized in whole units: most switches, routers, firewalls and patch panels are 1U, many servers are 1U or 2U, and UPS units are commonly 1U to 3U, sometimes with extra battery packs alongside.

Common rack heights

HeightMounting spaceWhere you see it
6U to 15U10.5 to 26.25 inWall-mount cabinets and small comms closets
24U to 27U42 to 47.25 inHalf-height racks for small offices and branch sites
42U73.5 inThe most common full-height rack in server rooms and data centers
45U and 48U78.75 and 84 inTaller racks where the ceiling and floor loading allow

Mounting space is the units times 1.75 in. The outside of the rack is taller because of the frame, top panel and casters or leveling feet, so check the maker's figure against door and ceiling heights.

How rack units are numbered

Most racks are numbered from the bottom, so U1 is the lowest unit and a 42U rack's top unit is U42. Some makers print the numbers from the top instead. Whichever way your rails are printed, use the same direction in the drawing. A device's position is often given as its lowest unit (a 2U server "at U20" fills U20 and U21) or as the range, which is how this planner labels it.

Rack layout tips

Questions

How tall is 1U?

One rack unit (1U) is 1.75 inches (44.45 mm) of vertical space, as set by the EIA-310 standard for 19-inch racks. A 42U rack has 42 of them, about 73.5 inches of mounting space. The outside of the rack is taller than that because of the frame, top and casters.

Are rack units numbered from the bottom or the top?

Most racks and most data center documentation number from the bottom, so U1 is the lowest unit. Some rack makers print the numbers from the top down. Check the numbers printed on your rails and use the same direction in your drawing, or the U numbers in your notes will point at the wrong slot.

How do I estimate the power a rack draws?

Add up the watts of each device, then divide by the circuit voltage to get amps (2,000 W is about 16.7 A at 120 V or 8.7 A at 230 V). Nameplate and power supply ratings are maximums; measured draw is usually lower. For circuit sizing, use the manufacturer's figures or measure, and follow your local electrical code and an electrician's advice.

What should go at the bottom of a rack?

The heaviest gear: UPS units and their battery packs, then large servers and storage. A low center of gravity makes the rack more stable, and it keeps the heaviest lifts close to the floor. Patch panels and switches usually go near the top, where the cabling enters.

Is my rack layout sent anywhere?

No. The planner runs on this page in your browser, and the page has no analytics or tracking. The layout is kept in the part of the link after the # so you can share it, and browsers never send that part to the server.